Main features

  • 10 digital input channel 24 Vdc ± 25%
  • 10 digital output channel 24 Vdc max 0.5A
  • Total output current max 5A

Available resources

Brochure
Automation platforms
Gefran product range brochure

Catalogue
4.0 plastic application catalogue

Flyer
G-MATION G3 – Flyer

Datasheet
G3-EU20 – Datasheet

Fieldbus Configuration Files
G3-EU20 – ESI Configuration file – V01
G3-EU20 – ESI Configuration file – V02

User Manual
G3-EU20 – User manual

User Manual
UL Certification – G3
EU Conformity Declaration – G3
UK Conformity declaration – G3

Technical specifications

Overview

The G3-U20 module has 10 digital input 24Vdc and 10 optically isolated, current-source digital outputs at 24 Vdc max 0.5A for channel.
Can be directly power loads in VdcC within the limits of rated currents, or control loads of any kind via solid state relay, contactors.
Digital input 9 and 10 can be configured as frequency signal reading G3-EU20 can be connected with all the G-Mation gateways and CPU’s from which it receives power supply.
Each output is protected against short-circuit, overload and overheating.
There is an Internal demagnetization circuit for inductive loads.