Valves and solenoid valves Series NA

3/2 – 5/2 – 5/3-way CC CO CP
with holes configured according NAMUR standards
The pneumatic interface connection complies with NAMUR standards.
These solenoid valves can be equipped with solenoids that are in compliance with UL or ATEX standards.

General Data

ConstructionSpool type (servo-pilot operated)
Valve functions3/2-way NC, NO – 5/2-way – 5/3-way CC, CO, CP
MaterialsAL body – stainless steel spool – NBR seals
MountingThrough 2 Ø5 holes in the valve body
Ports2 – 4 = NAMUR
1 – 3 – 5 = G1/4
InstallationDirectly on a Namur Interface
Operating temperature0 ÷ 60°C (using dry air -20°C)
Operating pressure1,5 – 10 bar double solenoid
2,5 – 10 bar single solenoid
Nominal pressure6 bar
Nominal flowQn = 1300 Nl/min
Nominal diameter Ø [mm]8 mm
FluidFiltered air without lubrication. If lubricated air is used, it is recommended to use ISOVG32 oil, and to never interrupt the lubrication.

Coding Example

NA54N1502ILU77
NASERIES
NAMUR
5NUMBER OF WAYS – POSITIONS
3 = 3/2 NC
4 = 3/2 NO
5 = 5/2
6 = 5/3 CC
7 = 5/3 CO
8 = 5/3 CP
4NPORTS
4N = G1/4 supply
Ports according NAMUR standards
15ACTUATION
11 = Double solenoid
15 = Single solenoid, spring return
33 = Pneumatic pneumatic
35 = Pneumatic, spring
02SOLENOID INTERFACE
02 = Mech. sol. 22 x 22
ILTYPE OF MANUAL OVERRIDE
= Bistable, standard
IL = Bistable, lever type (available on demand)
IM = Monostable (available on demand)
U7SOLENOID MATERIAL/SOLENOID DIMENSIONS
A8 = PPS/30 x 30
G7 = PA/22 x 22
G8 = PA/30 x 30 (24 V DC only)
G9 = PA/22 x 58
H8 = Self-extinguishing PA, Explosion-proof/30 x 30
U7 = PET/22 x 22
7SOLENOID VOLTAGE