Extra Information
Display | Analog indicator, operation and alarm ststus LED |
Accuracy | ±1.0% at ambient temperature +20°C (Indicator) ±2.5% at ambient temperature -20°C / +60°C (Indicator) ±0.25% at ambient temperature 0°C ~ +50°C (Current output) |
Scale range | -0.1 ~ 0.1 MPa to -0.1 ~ 1.2 MPa |
Working temperature | Ambient : -20 ~ 65 °C (Gas phase) Storage : -50 ~ 60°C maximum |
System configuration | HART communication |
Degree of protection | EN60529/IEC529/IP67 |
Standard Features
Mechanical
Pressure connection | Stainless steel (316SS) |
Element | Stainless steel (316SS) C-type bourdon tube |
Case and cover | Stainless steel (304SS) Bayonet type |
Window | Safety glass |
Movement | Stainless steel (304SS) Bimetal link (Temperature compensation) |
Pointer | Black painted aluminium alloy |
Process connection | G½” |
Helium leak rate | Tested to confirm leakage rates of less than 10-8 mbar L/sec |
Electrical
Input power and current consumption | 12 ~ 36 V DC input, Max. 60 mA@DC 24 V |
Display | Operating and alarm status LED |
Parameter input | HART configurator |
Output | Current output (4 ~ 20 mA, DC) One instantaneous pressure rising alarm relay Three pressure limit alarm relay |
Relay contact rate | Contact resistance : Max. 70MΩ Contact rating : 2 A 30 VDC, 0.5 A 125 DC (Res.load) Max switching voltage : 220 VDC / 250 VAC Max switching power : 60 W / 62.5 VA |